HVAC ELECTRONICS & CONTROLS

BSQ180 Series

Three-phase compressor control with air- and liquid-cooled variants

The SAMYOU BSQ180 Series provides three-phase inverter control for compatible DC inverter compressors in heat pump and air-conditioning systems. Air-cooled and liquid-cooled variants cover maximum input power from 9 to 11.5 kW and compressor output current from 20 to 24 A. Sensorless FOC, SVPWM, MTPA, and field weakening are combined with RS-485 Modbus RTU communication. An STO-equipped configuration is available as BSQ180D2.

Up to 11.5 kW Maximum Input Power (variant-dependent)
Up to 24 A Maximum Compressor Output Current (variant-dependent)
Three-phase AC Input Supply
RS-485 Modbus RTU

Key Features

  • Sensorless compressor control

    Field-oriented control (FOC) with space-vector pulse-width modulation (SVPWM).

  • Dual closed-loop regulation

    Separate speed and current loops regulate compressor operation.

  • Torque control

    Maximum torque per ampere (MTPA) control uses the compressor motor's reluctance torque characteristics.

  • Extended operating range

    Field weakening supports operation within the matched compressor's permitted speed range.

  • Controlled starting

    Closed-loop starting adjusts starting torque to the load. Compressor matching is required.

  • Host-controller integration

    Asynchronous half-duplex RS-485 communication using Modbus RTU.

Technical Specifications

Electrical
Input supply 380 VAC line-to-line, +20% / -15%
Supply phase Three-phase
Input frequency 50 / 60 Hz
Maximum input current Up to 20 A at 380 VAC; variant-dependent
Maximum input power Up to 11.5 kW; variant-dependent
Maximum compressor output current Up to 24 A; variant-dependent
Compressor speed range 10-160 rps; compressor-dependent
Carrier frequency 5 kHz
Full-load drive efficiency ≥97%
Control & Communication
Motor control Sensorless FOC with SVPWM; dual speed and current loops
Torque strategy Maximum torque per ampere (MTPA)
Field weakening Supported; compressor-dependent
Communication Isolated RS-485, asynchronous half-duplex; Modbus RTU
Mechanical & Environmental
Cooling Air or liquid cooling; variant-dependent
Mechanical dimensions See model-specific drawings
Operating temperature -35 to +60 °C
Storage temperature -40 to +85 °C
Operating humidity 10-95% RH; no frost or condensation
Altitude No derating below 1,000 m; derate by 1% per 100 m above 1,000 m; maximum 4,000 m

Available Models

Compare configurations for your application requirements.

ModelConfigurationInput VoltageKey FeatureDimensions
BSQ180D2 Air-cooled 380 VAC +20% / -15% Input: 15 A; input power: 9 kW; output: 20 A; STO-equipped See model-specific drawing
BSQ180B2F2 Air-cooled 380 VAC +20% / -15% Input: 15 A; input power: 9 kW; output: 20 A; Without STO See model-specific drawing
BSQ180B2 Air-cooled 380 VAC +20% / -15% Input: 17 A; input power: 10 kW; output: 22 A; Without STO See model-specific drawing
BSQ180B2Y1 Liquid-cooled 380 VAC +20% / -15% Input: 20 A; input power: 11.5 kW; output: 24 A; Without STO See model-specific drawing

Engineering Resources

View Technical Datasheet

Mechanical Drawing
BSQ180 connection
Connection Diagram

OEM ENGINEERING SUPPORT

Need Help With Your Application?

Share your system requirements, integration needs, or product evaluation plans with SAMYOU. Our team can discuss suitable solutions for your project.