HVAC ELECTRONICS & CONTROLS
BSQ560 Series
Three-phase compressor drive with liquid-cooled output up to 55 A
The SAMYOU BSQ560 Series is a three-phase inverter drive platform for compatible DC inverter compressors in heat pump and air-conditioning equipment. Air-cooled variants support up to 25 kW input power and 50 A output current. The liquid-cooled BSQ560A1Y1 supports up to 30 kW input power and 55 A output current. Sensorless FOC, SVPWM, MTPA, and field weakening support compressor control, with RS-485 Modbus RTU communication and an STO-equipped BSQ560A2F1 option.
Key Features
Sensorless compressor control
Field-oriented control (FOC) with space-vector pulse-width modulation (SVPWM).
Dual closed-loop regulation
Separate speed and current loops regulate compressor operation.
Torque control
Maximum torque per ampere (MTPA) control uses the compressor motor's reluctance torque characteristics.
Extended operating range
Field weakening supports operation within the matched compressor's permitted speed range.
Controlled starting
Closed-loop starting adjusts starting torque to the load. Compressor matching is required.
Host-controller integration
Asynchronous half-duplex RS-485 communication using Modbus RTU.
Technical Specifications
| Electrical | |
|---|---|
| Input supply | 380 VAC line-to-line, +20% / -15% |
| Supply phase | Three-phase |
| Input frequency | 50 / 60 Hz |
| Maximum input current | Up to 50 A at 380 VAC; variant-dependent |
| Maximum input power | Up to 30 kW; variant-dependent |
| Maximum compressor output current | Up to 55 A; variant-dependent |
| Compressor speed range | 10-160 rps; compressor-dependent |
| Carrier frequency | 4-8 kHz |
| Full-load drive efficiency | ≥97% |
| Control & Communication | |
| Motor control | Sensorless FOC with SVPWM; dual speed and current loops |
| Torque strategy | Maximum torque per ampere (MTPA) |
| Field weakening | Supported; compressor-dependent |
| Communication | Isolated RS-485, asynchronous half-duplex; Modbus RTU |
| Mechanical & Environmental | |
| Cooling | Air or liquid cooling; variant-dependent |
| Mechanical dimensions | See model-specific drawings |
| Operating temperature | -35 to +60 °C |
| Storage temperature | -40 to +85 °C |
| Operating humidity | 10-95% RH; no frost or condensation |
| Altitude | No derating below 1,000 m; derate by 1% per 100 m above 1,000 m; maximum 4,000 m |
Available Models
Compare configurations for your application requirements.
| Model | Configuration | Input Voltage | Key Feature | Dimensions |
|---|---|---|---|---|
| BSQ560A1 | Air-cooled | 380 VAC +20% / -15% | Input: 42 A; input power: 25 kW; output: 50 A; Without STO | See model-specific drawing |
| BSQ560A1F2 | Air-cooled | 380 VAC +20% / -15% | Input: 42 A; input power: 25 kW; output: 50 A; Without STO | See model-specific drawing |
| BSQ560A2F1 | Air-cooled | 380 VAC +20% / -15% | Input: 42 A; input power: 25 kW; output: 50 A; STO-equipped | See model-specific drawing |
| BSQ560A1Y1 | Liquid-cooled | 380 VAC +20% / -15% | Input: 50 A; input power: 30 kW; output: 55 A; Without STO | See model-specific drawing |